Laserfiche WebLink
KITTITAS COUNTY SOLID WASTE ON-CALL <br />CLE ELUM TRANSFER STATION TANK REPLACEMENT <br /> SEPTEMBER 2025 Wastewater Tanks <br /> 333413 - 2 <br /> <br />SECTION 333413 <br />WASTEWATER TANKS <br />PART 1 GENERAL <br />1.01 SECTION INCLUDES <br />A. Wastewater underground storage tank and appurtenances. <br />1.02 RELATED REQUIREMENTS <br />A. Section 312316 - Excavation <br />B. Section 026500 – Underground Storage Tank Removal. <br />1.03 SUBMITTALS <br />A. See Section 013000 - Administrative Requirements, for submittal procedures. <br />B. Product Data: Provide data on pipe, manholes, and any associated tank accessories. <br />C. Manufacturer's Installation Instructions: Indicate special procedures for septic tank installation. <br />D. Project Record Documents: Accurately record actual locations and inverts of buried pipe, <br />components, and connections. <br />1.04 QUALITY ASSURANCE <br />A. Comply with applicable code and regulations for work of this section. <br />PART 2 PRODUCTS <br />2.01 WASTEWATER HOLDING TANK AND APPURTENANCES <br />A. ASTM D4021, UL 1316, double wall fiberglass underground holding tank for storage of <br />graywater, and corrosive and reactive liquids. H-20 vehicle load rated when buried to depth. <br />Tank to be equipped with lifting lugs, hold-down straps, and tappings for accessories. <br />Deadman anchors as shown on drawings. <br />B. Manufacturers: <br />1. Premier Production Equipment Double Wall Decontamination Tank, or approved equal. <br />C. Tank Capacity: 5000 gallon (18,927 liter). <br />2.02 BEDDING AND BACKFILL MATERIALS <br />A. Provide bedding and backfill materials as specified on plans and as required per tank <br />manufacturer specifications. <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br />