Laserfiche WebLink
Exhibit c (2) <br />Received 1-28-2015 as an email 4.31 pM <br />Jerry, <br />Based on the information that you have provided me I have estimated that the minimurn fire flow <br />would be: <br />Residential Townhouses 3501 sq feet and greater with automatic sprinklers = t hour flow duration and <br />1000 Gallons Per Minute. This is considering a Type V wood-frame construction, <br />The larger RV storage appears to be a Type lllA ordinary construction - 20,000 sq ft = 2000 x 0.25 <br />{Sprinklers) = 500. {Cannot reduce less than 1000 GPM per IFC). The fire flow would be 1000 GpM for <br />2 hour llow duration, <br />L000 GPM flow rate for 2 hours or 120,000 total water needed for fire suppression. <br />ln reference to your hydrant questions, IFC 507.5.1 allows maximum spacing of 600 feet for the <br />hydrants, since the buildings will be sprinkled. The RV storage building should have a hydrant within 600 <br />feet of it. <br />Tha n ks, <br />Patrick Nicholson <br />Fire Marshal <br />Kittitas County <br />41i" N Ruby Sl, Suite 2 <br />Ellensbtirg WA 98926 <br />is09) 8e9-3ssa (cell) <br />(s09)952-7000 {oflice} <br />oat.nicholson@co.kittita{.wa.us