Laserfiche WebLink
A.1.9 DMB - Stub Detail <br />GROUND LEVEL <br />05 im <br />=4 <br />�m <br />48" MAX <br />30" MIN — { <600V) <br />36" MIN — ( >600V ) <br />,s <br />7 <br />f <br />1 <br />2,3,4, OR 6" SCH 40 PVC ' <br />7' RED "UG POWER" <br />WHISKER <br />(STOCK #303154) <br />4" RED MARKER BALL` <br />(STOCK #303155) <br />I CAP NOT GLUED <br />—STRING OR TAPE TIED <br />�— TO CAP RING OR FOLDED <br />OVER TOP OF CONDUIT <br />UNDER CAP <br />*INSTALL THE MARKER BALL AT LEAST 6" ABOVE OR TO THE SIDE OF METALLIC OBJECTS. <br />*No METAL OBJECTS (INCLUDING CABLE) ABOVE RED MARKER BALL. <br />*PLACE SAND OR SOFT NATIVE SOIL OVER MARKER BALL TO PROTECT IT DURING BACKFILL. <br />CITY OF ELLENSBURG <br />PUBLIC WORKS & UTILITIES <br />LIGHT DEPARTMENT <br />CREATED BY : TG CREATED DATE: i irm2020 <br />APPROVED BY: PM REVISED <br />PAGE # SCALE : NTS <br />PVC CONDUIT STUB <br />WITH MARKERS <br />DUCT MARKER BALL <br />DMB <br />Page 20 <br />JOB #3450-316 FAIRGROUNDS RV PARK 3PH EXTENTION, DEVELOPERS AGREEMENT <br />